Fire Alarm Maintenance Management System

Fire Safety is a legal requirement under the Fire Safety Order 2005. People are now going to prison under this piece of legal legislation, for not taking their responsibilty seriously and risking the lifes of thier employees, staff and people under their care.

Therefore, the introduction of the FSO must changed the way we manage our fire safety maintenance duties. It is important that all documentation involving maintenance, testing, remedial works, call outs, fire risk assessments, etc. are logged and backed up in a responsible way. Should a fire incident occur at your premises the authorities will expect to see your records confirming you have abided by the Fire Safety Order 2005. Our fire alarm maintenance management system helps you to manage this additional legal responsibility.

Is your current maintenance provider carrying out your fire alarm maintenance visits on time? Is all the documentation stored and backed up should the need arise to produce such documentation?

Posted in Uncategorized | Leave a comment

Fire Alarms and Smoke Fire Dampers

Fire Alarms and Smoke Fire Dampers

In large commercial and industrial buildings, Fire alarms play an important role to ensure the fire compartmentation is maintained in the event of fire.

In these types of buildings, airflow for heating and ventilation is essential. However, to create such airflow, will require the air traveling through fire barriers. In the event of fire, the same paths could be used to spread fire and smoke throughout the building.
The solution to provide the required airflow for heating and ventilation during the normal operation of the building, and to enforce the compartmentation in the event of fire, is to install smoke dampers within each ductwork passing through the fire barrier. The smoke dampers are connected to the fire alarm panel usually via a smoke damper panel.

Fire Systems Ltd, design, installed and commission fire smoke damper systems as shown on the video.

In this video, Fire Systems Ltd, working for NG Bailey Rail, supplied and installed two twelve way Kentec smoke damper panels connected to eighteen “Actionair” smoke fire dampers.
The dampers have micro switches fitted to the ‘open’ and ‘closed’ positions. The outputs from these switches are connected to the damper panel.

All the fire alarm and smoke damper wiring was carried out in “FP Plus,” which is a fire rated enhance cable. The cables were given further protection as they were installed within galvanized trunking and tube.

The close-up view shows the “Action Air” damper in the closed position; this is shown by the black lever in the top position. The damper opens up when a 24v DC voltage is applied. On removing this voltage either by a fire alarm activation or a power cut the damper will close within the allocated 140 second window and stop any potential smoke or fire from transferring from one fire compartment to another and limit the spread of fire.

To ensure the fire dampers are given as much time as possible to close, detectors are installed within the ceiling void and at the room ceiling level. Another important point to consider is the sealing of any holes going through the fire barriers, as holes no matter the size can allow the smoke and fire to jump between zones.

During the test as shown here, in status normal with the dampers in the open position, the LED’s within the damper panel will be green. On activation of the fire panel, simulated by our engineer activating a manual call point, the dampers have a window of 140 seconds to change from the open to the closed position. This is indicated by the LED’s changing to red. However, if any damper has not changed from the open to the closed position within the allocated time the damper panel will send a fault signal to the fire alarm panel.
These particular dampers are held open by a constant 24v dc supply coming from the fire damper control panel. If the dampers lose the 24v supply, either by the damper panel receiving a fire alarm activation from the fire alarm panel, or by a power failure, the dampers will lose its power and close. The arrangement is what we called ‘fail safe’. Once power is restored to the dampers, they will reopen.

For more information of fire smoke dampers why not contact our office on 020 8541 5646 or visit our website on www.firesystems.co.uk and complete our contact form. We also provide fire alarm servicing for all types of fire alarm equipment.

Posted in Fire alarm installations | Leave a comment

Fire Systems Ltd – London Underground & Substation Fire Alarms

Fire Systems Ltd, is a well established fire alarm company and has carried out works for London Underground and Power Network companies.

We are currently involved in the fire alarm upgrade or complete new installations for substations throughout London and the Southeast. To be in a position to carry out such work for large corporations, the fire alarm company must have a good reputation, highly skilled work force, motivated management team, take health and safety very seriously and have a robust quality assurance structure to ensure you are able to handle the rigorous requirements imposed in working in such an environment.

 

As you can see from this short video clip, it is important that the fire alarm company has installation engineers who are capable of installer fire alarms to a very high standard. Installing a fire alarm in a substation is totally different from installing one in your standard commercial property. The installation in a substation is vetted, and quality checked by qualified London Underground or the Power network Fire Engineers, who carried out a rigorous inspection. The inspectors understand the quality expected and will fail any part of the installation if it is not to the required standard.

When installing fire alarms in substations or London Underground all fire alarm wiring has to be carried out using ‘Enhanced’ fire rated cables. This can be in the form of MICC or in soft skin“Enhanced” fire rated cable. The cable we use is “FP Plus” or Draka Firetuf cables. However, even though the cables are of an enhance standard, the specification also requires that the cables are mechanical protected even further with galvanized tube for any drops to a lower level such as for manual call points or sounders. Cables at high level will be clipped on a tray or depending on the specification metal tie wraps may be used.

All equipment for such projects must be on London Undergrounds approval list or approval must be sanctioned for any equipment not on the list.
On this particular project the fire alarm panel will be the Kentec Syncro and the detection protocol will be Hochiki.

Fire Systems Ltd, have been designing and installing fire alarm systems since 1992. During this time, we have worked on many London Underground and substation’s power projects. If you have any projects of this nature and require a competent fire alarm company to carry out the design, installation and commissioning, contact our office on 020 8541 5646 or visit our website on www.firesytems.co.uk and complete our contact form.

Posted in Fire alarm installations | Leave a comment

Wireless Fire Alarm Protecting Olympics staff

In East London close to the Olympic Stadium a small temporary village is erected.

The village consisting of 130 cabins, Kitchen, recreation area, laundry room, welfare area and small substation, is being used to house staff during the Olympics.
The cabins were to sleep 4 people; therefore the total site had the capacity to accommodate 520 people.

The health and safety consultants responsible for the site, insisted on all cabins having smoke detectors with sounders, with each cabin having a link back to a security office based on the site.

Well, as you can appreciate using a wired system was not an option. Therefore, our client contacted Fire Systems Ltd who is a specialist wireless fire alarm company and well known for our wireless fire alarm solutions within the fire alarm industry.

The final design comprised of 15 wireless base stations, 150 wireless base sounders and detectors, wireless sounder beacons in out buildings and washing areas, 12 manual evacuation points. These points would consist of a wireless manual call point and sounder beacon with a couple of fire extinguishers.

On completion of the installation, we programmed the cause and effects as follows: activation of a smoke detector within a cabin would activate the sounder within the cabin of origin only, activate the two fire alarm panels and alert security on site and start a 3 min timer. The 3 min timer allows the security on site to investigate the activation, if the it turns out to be a false alarm, the fire alarm panel is silenced and reset. However, if the alarm is not acknowledged within the 3 min time window, the effected fire zone of about 20 cabins will go into full evacuation, or the security personnel can make the decision and override the 3 min timer and evacuate the site.

The wireless devices could communicate with their base stations easily, and some of the cabins were of a “vandal” proof construction and made out of metal! But this proved to be no problem for the equipment we were using.

Fire Systems Ltd, now lease and hire wireless fire alarm equipment for temporary constructions such as this. We also carry our fire alarm servicing and maintenance on all types of fire alarms systems.

For more information, why not contact our office on 020 541 5646 or visit our website on www.firesystems.co.uk and complete the contact form.

Posted in Wireless fire alarms | Leave a comment

Hochiki acquires fire alarm panel manufacturer Kentec Electronics

It’s official, after 25 years and after becoming the UK’s number one independent fire alarm panel manufacturer, for some reason unknown to me, Kentec has been acquired by the Japanese detection manufacturer Hochiki Corporation.

The statement announcing the acquisition is very vague. It states that Hochiki Corporation has entered into an agreement to acquire the stock of Kentec Electronics. The transaction will be completed on the 1st October 2012.

Hochiki who has been manufacturing fire detection equipment since 1981, is one of the leading fire detection companies in the UK. Acquiring Kentec will undoubtedly increase their market share. From the reports, I have read, Kentec will continue to operate from its main location in Dartford and will be mostly unaffected by the acquisition.

Kentec, rivals such as Advance Electronics who were established in 1999 have been growing and taking market share from Kentec. However, Kentec has been around for years, has a reasonable reputation and client base. With their latest product coming to market the long awaited ‘Takis’ panel, you would think all was looking good for the future, so why sell? I have seen a statement stating, “Kentec Electronics believes this is an opportunity to further develop its business and allow access to new markets world-wide” Maybe that is the reason, only time will tell.

Over the years Kentec has been the number one choice for fire suppression panels and associated equipment. The popular Sycro range of equipment has served us well, but is coming to the end of its shelf life and investment for the future has gone into the long awaiting ‘Takis’ panel, starting with the four loop fire alarm panel. From sources, the ‘Takis’ is going through the approvals’ process, but with the panel having so many ground-breaking features, it is taking longer than expected. Sources tell me, It is due out in the first quarter of next year.

I wonder how the rivals of Hochiki (Apollo, Argus), and Kentec (Advance, Morley, Kidde etc), view this takeover.
I would imagine Kentec would have sensitive information as they produce panels for Hochiki’s rivals, how would this be managed?

If anyone has any information regarding this acquisition, please complete the comment section on this blog page.

Fire Systems Ltd, an independent fire alarm company, supplies and installs fire alarm equipment from all supplies choosing the best products to suit our clients as we are not ‘tied’ in or contracted to any manufacturer.
We offer a competitive fire alarm maintenance and installation service. For more information contact our office on 020 541 5646 or visit our website on www.firesystems.co.uk

Posted in Fire alarm information | Leave a comment

Fire Alarm – Air Sampling – London Underground train depot – Video

In this video, we focus on an Air sampling detection system designed. On this particular project the air sampling system showed, is designed, supplied and project managed by Fire Systems Ltd and is part of a London Underground project.

In this particular design, there are two large sheds joined together both approximately 160m long and 20m wide. We have divided the two sheds into four zones, giving a total of eight zones. Each zone in length is approximately 40m.

The detectors used on this project is the Stratos HSSD 2 manufactured by Airsense Technology. This particular model I believe is their largest detector of their product range. It can provide four sampling pipes with a total distance between the pipes of 200m (for example, example 4 x 50m. Stratos also manufacture a Micra 25 and a Micra 100.

The eight detectors are to be interfaced onto the loop using Stratos APIC interface cards. These cards replace the typical fire alarm interface input/output units and are able to provide additional information at the main fire alarm control panel. The fire alarm protocol for this project is Hochiki as this is standard protocol used on London Underground.

When designing a fire alarm system, one of many decisions that have to be made, is what is the must suitable type of detector for the area to be protected.

Air Sampling systems are renown for provided early warning in the event of fire. The earlier the fire is detected, the earlier the alarm can be raised to give occupants more time to escape, or if possible extinguish the fire prevented less damage to property. Where large areas are to be protected the choice is usually between a beam detector and an air sampling detector.

The air sampling system consists of lengths of pipe with strategically placed sampling holes along its length. A detector with an air pulling device sucks the sampled air into the detector measuring chamber. The air is sampled and if there is a presence of smoke particles an alarm is raised by the detector. The air sampling detector is usually part of a larger fire alarm system and on activation of the detector a signal is transmitted to the fire alarm panel and the alarm is raised. An air sampling detector is more sensitive then your standard smoke detector, and this can be as much as 10 to 200 times.

There are other manufactures of air sampling systems and the biggest manufacturer is Vesda from Xtralis.
Vesda have the LaserFOCUS, Laser COMPACT, LaserPLUS and the LaserSCANNER and ICAM .

There is also Wagner who manufacture Titanus

Posted in Uncategorized | Leave a comment

Wireless fire alarms Detectomat

Back in October 2011, Fire Systems Ltd, showed on our blog and Youtube channel some of the first pictures of Detectomat’s new wireless fire alarm system the SRC 4000. We were expecting the launch of the new system the first quarter of this year, but so far we are still awaiting the launch.

Detectomat had the SRC 4000 on display at Firex South, but were unable to confirm when it will be entering the UK market. Due to the enforcement in March 2011 of the new Radio fire alarm code EN54-25, the SRC 4000 is being developed to ensure Detectomat can continue to compete in the UK market. Their current wireless fire alarm system the SRC 3000 does not comply with the new standard. However, it can still be used on certain small applications following a fire risk assessment and consultation with the authorities.

Reviewing the specification of the panel and it is quite impressive.
It has:
• Integral self-learning, which completely automates the system, set up task.
• Radio-mesh communication; Radio transmission is supported via alternative pathways to provide the highest level of radio integrity between the network and devices.
• Fully approved; the system components have been third party certified and approved to EN54 guidelines.
• The SRC 400 panel utilizes a unique, data protected protocol with a special transmission mode to avoid data collision.
• Optimized energy consumption, and this means that no lithium batteries are required.

However, stating a list of impressive features and bringing the product to the market is a different proposition.

Detectomat is known for a cost effective wireless products and we are hoping this latest Radio fire alarm will follow suit.

Detectomat’s competitors; Hyfire, from Sterling, Firecell from EMS and Zerio Plus from Electro Detectors EDA all currently have compliant wireless fire alarm system on the market.

If we hear on more from Detectomat we will let you know.

For more information on wireless fire alarms why not call our office on 020 8541 5646 or visit our website on www.firesystems.co.uk and complete our contact page.

Posted in Fire alarm installations, Wireless fire alarms | Leave a comment

Video-Fire alarm – New Sports Hall ACS Egham

ACS Egham is in the process of building a new state of the art sporting facility.

Fire Systems Ltd, who currently carries out the fire alarm maintenance for the school, secured the order to carry out the fire alarm enabling works and installation of the new addressable fire alarm system.

Before, the new building was erected; the old sport hall had to be demolished. The old sports hall was joined to another building known as the Cedar block. One fire alarm system protected both buildings, there were no drawings identifying the fire alarm wiring, so the enabling works involved tracing and removing all the fire alarm wiring in the existing sports hall while retaining the fire alarm wiring to the other half of the building. The enabling works was successful and the old sports hall was demolished.

Fire Systems Ltd, was involved in the designing of the new system, we decided on an L1 category system due to the amount of people that may be occupying the building at any one time as this the new sporting facility has a large seating area for major sporting events.

The fire alarm system to be installed is a Morley Addressable from the ZXe range, with Apollo protocol. The reason we choose the Morley fire alarm system is the school already had an existing Morley networked fire alarm system. The school has very large grounds with numerous amount of out buildings. These buildings are protected by the Morley network and there are currently eleven addressable fire alarm panels networked and this new panel will make it number twelve. Having all twelve panels on a network allows the security to monitor all the outbuildings in the event of fire and evacuate any building remotely or automatically.
As you can see from the video this is a state of the art sporting complex. The main sports hall and the offices off of the hall are protected by Apollo smoke detectors with base beacon sounders. All exits from the hall and to the open air have an addressable manual call point.

This new facility will promote a wider recreational offer, including a dance studio, fitness suite, two FIBA basketball courts and an indoor climbing wall. This new building will also provide an opportunity to redevelop and change the use of their existing Gym into a large, flexible space for drama, dance, musical performance, assemblies, exhibitions, meetings, and Lower School activities.

During the building works the construction site had to be protected against fire, wireless fire alarm evacuation points were installed at various positions throughout the construction site. In the event of a fire incident on the site the wireless fire alarm point can be activated, evacuating the site and alerting the fire marshalls in the event of fire.

For more information contact our fire alarm company on telephone number 020 8541 5646 or visit our website on www.firesystems.co.uk and complete our contact page.

Posted in Fire alarm installations | Leave a comment

Video – Fire Suppression System (FM200) Overview

This video is a brief explanation of the operations of a fire suppression system.

In its simplistic terms, a fire suppression system, is the combination of a fire alarm system connected to a fire extinguisher.
The fire alarm section of the system detects the fire or smoke and then sends a signal to the fire extinguisher which automatically activates and puts the fire out.

In this video, the area being protected is a small Comms Room and the fire suppression agent on this system is FM200.

To enable us to hear what I am saying during the video, we have removed the gongs of off the fire bells within the Comms Room and isolated the outputs to the main fire alarm panel.

Within the protected area is a series of smoke detectors, in a room this size, there are four on the ceiling and four in the floor void.

The four detectors are divided into two separate zones; therefore, two detectors are in zone 1, and the remaining two detectors are in zone 2.

The fire suppression system has a 1st and 2nd stage, if one detector activates the bell sounds, red beacon flashes, informing the occupants that the system is now in stage 1 a signal is sent to the main house fire alarm system, and any room dampers will close. If a second detector were to operate in an alternative zone, this will put the system into stage 2.

As you can see at the engineer has removed the actuator from the cylinder, as we do not want a discharge while carrying out this test.

In stage two the electronic pulsing sounder begins, and a blue flashing beacon illuminates. When the system is in stage 2, the room is now ready for the gas discharge, and a 30-second countdown timing sequence begins before the fire suppression agent in this case FM200 will automatically discharge within the protected area.

In stage 2, all occupants should have left the room, and the door should be closed behind them.

At the front of the panel, you can see the timer countdown before the gas is discharged.

For this demonstration, we have removed the actuator from the cylinder, but to show you that the actuator has fired; we have placed a screw driver within the solenoid. During normal operation, the solenoid is energized and therefore will grip the screwdriver, however, once the fire suppression system has activated the solenoid, the magnetic force is released, and the screwdriver will drop to the floor.
Finally, there are two other elements to discuss. The first is the pressure relief damper, and the 2nd is the smoke extract.

The pressure relief damper is the white square unit on the wall. The unit is similar to a “cat flap” and is designed to open at a certain room pressure. This is required because during gas discharge, there can be enough force from the pressure generated by the discharge of the gas to damage the structure of the room. Another point to consider is when the smoke extract is operated, a negative pressure is generated, and you will see this when we operate the smoke extract system.

The round circular unit next to the pressure relief damper is the smoke extract. This unit is required to extract the discharged fire suppression agent in this case FM200 and any smoke that may be trapped within the protected area.
As we operate the smoke extract you will notice the pressure relief damper open.

This completes our overview of a fire suppression system, if you require assistance in the design, installation or maintenance of fire suppression systems why not contact our office on 020 8541 5646 or visit our website on www.firesystems.co.uk and complete our contact form.

Posted in Fire Suppression | Leave a comment

Fire Risk Assessor – The Law CPD Day – FIA

Fire Risk Assessor – The Law CPD Day – FIA

Since the introduction of The Regulatory Reform Order in 2005, the need for Fire Risk Assessors has dramatically increased. This is due to the legal requirement of the order that the majority of commercial properties and some residential such as HMOs, must carry out a fire Risk Assessment.

 

However, even though the order has been in force for seven years, there appears to still be confusion at all levels from the courts, fire brigade and the Fire Risk Assessors as to how the order should be enforcing fire safety in England and Wales.

Fire System Ltd, attending a (Fire Risk Assessor – The Law “CPD” day.) CPD stands for the “Continuing Professional Development.”

The presenters were Kizzy Augustin, a lawyer from Pinsent Masons LLP and the highly respected Colin Todd from C.S Todd and Associates Ltd.

The day centre around the legal responsibilities of Fire Risk Assessor and the “Responsible Person” who in the majority of cases is the employer.

It was an informative day and was attended by Fire Risk Assessors and fire alarm companies.

Fire System Ltd, continue to invest in this type of training to ensure we offer our clients up to date information, especially when it comes to the fire safety and the law.

For more information on Fire Risk Assessments, why not call us on 020 8541 5646 or visit our website on www.firesystems.co.uk and complete our contact form.

Posted in Fire Safety News items | Leave a comment